Duct Blaster Test Report
Zip-Ez Insulation Fasteners
Independent Leakage Test Certification • April 1, 2010
Tested by BPI-Certified HERS Rater using calibrated Minneapolis Duct Blaster with DG-700 gauge
ZIP-EZ™ fasteners were independently tested to determine if they contribute to duct leakage. A 12"×12"×8' section of 16-gauge sheet metal duct was sealed with duct mastic and tested using a Minneapolis Duct Blaster with DG-700 gauge at 25Pa, 50Pa, and 100Pa — before and after fastener installation. All results confirmed visually by fog machine and smoke pencil.
Test #1 — Baseline Before Installation Flow Ring #3
Pass — Zero Leakage
25Pa No leakage detected
50Pa No leakage detected
100Pa No leakage detected
Fog machine & smoke pencil: No visible leaks at any joint or seam
7 fasteners installed through 3" duct insulation sections, spaced 12" on center.
Test #2 — After Fastener Installation Through Insulation Flow Ring #3
Pass — Zero Leakage
25Pa No leakage detected
50Pa No leakage detected
100Pa No leakage detected
Fog machine & smoke pencil: No visible leaks detected
6 additional fasteners installed directly through sheet metal, no insulation, 12" on center.
Test #3 — Fasteners Direct Through Sheet Metal Flow Ring #3
Pass — Zero Leakage
25Pa No leakage detected
50Pa No leakage detected
100Pa No leakage detected
Flow restrictor removed — 100Pa retest: No leakage measured. Coarse screw threads appear self-sealing.
3
Independent
Tests
25–50–100 Pa
Pressures
Tested
0
Leaks
Detected
100%
Pass
Rate
American Made • Patented • 25+ Years
Duct Blaster Test Report — Conclusion
Page 2 of 2
Zero Measured or Visible Leakage
No leakage observed before or after installation at 25Pa, 50Pa, or 100Pa. Results independently confirmed by fog machine and smoke pencil at every stage. Coarse screw threads are self-sealing — no additional sealant or tape required.
Tony Lisanti
Certified HERS Rater / QA Designee
BPI Certified — Building Analyst, Envelope & Heating
Test Date: April 1, 2010
1
ZIP-EZ™ fasteners penetrate duct wrap and sheet metal without creating measurable air leakage.
2
Installations pass duct blaster tests — critical for energy code compliance and HERS ratings.
3
No additional sealing required at fastener penetration points — saving time on every job.
4
Independently confirmed for use in air-handling spaces — zero leakage detected at every pressure.
ZERO
Air Leakage
All Pressures
25+
Years
In the Field
USA
Patented
American Made
GreenSpec
Listed
Product
This test was conducted by an independent, BPI-certified HERS Rater using calibrated equipment within specification.
Full documentation available upon request • sales@jtproducts.com • 845.988.2000 • jtproducts.com